Tag: temperature

INCINERATOR SPECIFICATION Capacity UPTO 20 kg/hr

Size:  940 x860x2700 mm
Material:  STAINLESS STEEL STACK, REFRACTORY CONCRETE LINING SPECIAL INSULATION MATERIAL
With burner:  15 C 20 KW
Temperature:   PRIMARY CHAMBER = 800°C AND SECONDARY CHAMBER = 850 – 1200° C
Sufficient heat generation for secure and complete combustion 600-800 °C in the first chamber and >1000 °C in the second chamber
Easy transportation on standard EURO-pallets
Constructed in a modular fashion  easy on-site movement and assembly with a minimum of equipment and technical skills;
For the destruction of problematic waste like sharps, amputates and body parts, wet or moist matter;
Off-gas quality: moderate smoke emissions during one quarter of the total incineration time; no visible emission during three quarters. AS PER INTERNATIONAL STANDARDS 
The remaining ash approximately 5-10% in weight and below 1% in volume of the original waste AS PER INTERNATIONAL STANDARDS 
Chimney height at least 5 m above the incinerator 5m ABOVE FROM THE GROUND
Temperature resistance of the lining  at least 1,200 °C

INCINERATOR SPECIFICATION Capacity UPTO 20 kg/hr

Size:  940 x860x2700 mm
Material:  STAINLESS STEEL STACK, REFRACTORY CONCRETE LINING SPECIAL INSULATION MATERIAL
With burner:  15 C 20 KW
Temperature:   PRIMARY CHAMBER = 800°C AND SECONDARY CHAMBER = 850 – 1200° C
Sufficient heat generation for secure and complete combustion 600-800 °C in the first chamber and >1000 °C in the second chamber
Easy transportation on standard EURO-pallets
Constructed in a modular fashion  easy on-site movement and assembly with a minimum of equipment and technical skills;
For the destruction of problematic waste like sharps, amputates and body parts, wet or moist matter;
Off-gas quality: moderate smoke emissions during one quarter of the total incineration time; no visible emission during three quarters. AS PER INTERNATIONAL STANDARDS 
The remaining ash approximately 5-10% in weight and below 1% in volume of the original waste AS PER INTERNATIONAL STANDARDS 
Chimney height at least 5 m above the incinerator 5m ABOVE FROM THE GROUND
Temperature resistance of the lining  at least 1,200 °C

Supply, Installation and Commissioning of DIESEL FIRED INCINERATORS

Supply, Installation and Commissioning of DIESEL FIRED INCINERATORS
Medical Waste Incinerator, 100 to 120 Kg/hr
Application   For incineration, general and pathological
Capacity    100 C 120 kg/h burn rate
Type Two  combustion chambers type; primary  and Secondary, controlled/forced combustion air type with a flue gas emission scrubbing unit
Operating time                Minimum 8 hours daily
Operating temperature     From 850 0C to 1200 0C, Automatic controlled
Residual Ash                    5 to 10%
Construction Constructed from heavy duty mild or aluminized  steel
Or equal and approved equivalent

Insulation material            Refractory material lining similar or equal to calcium 
Silicate and hot face combination of heavy duty brickwork
Internal Construction        Fixed hearth type complete with gratings, concave bottom and charging door, lined with refractory material
Charging Door                   Suitable for manual loading of wastes and with smooth 
Dear seal equivalent of Ceramic seals with hinges.
Door Lock                          Automatic, Electric type
Ash removal door    Provided, for removing resultant bottom ash leftovers                              from the Primary chamber
Gratings    Provided
Loading Manual loading of waste
Primary Burner                        Fully automatic, with fuel, temperature and speed  controls with ignition system  flame detector                                                         Air fan Complete with safety features, flame failure                                                                    Diesel fired fuel injector type                                               
Flange mounted
Blower   Provided.  3 phase for supplying excess combustion air through the distribution system with speed control system
Temperature Minimum exit 850 0C
Observation port To be provided with protective glass type
     3.3    Secondary chamber

Supply, Installation and Commissioning of DIESEL FIRED INCINERATORS

Supply, Installation and Commissioning of DIESEL FIRED INCINERATORS
Medical Waste Incinerator, 100 to 120 Kg/hr
Application   For incineration, general and pathological
Capacity    100 C 120 kg/h burn rate
Type Two  combustion chambers type; primary  and Secondary, controlled/forced combustion air type with a flue gas emission scrubbing unit
Operating time                Minimum 8 hours daily
Operating temperature     From 850 0C to 1200 0C, Automatic controlled
Residual Ash                    5 to 10%
Construction Constructed from heavy duty mild or aluminized  steel
Or equal and approved equivalent

Insulation material            Refractory material lining similar or equal to calcium 
Silicate and hot face combination of heavy duty brickwork
Internal Construction        Fixed hearth type complete with gratings, concave bottom and charging door, lined with refractory material
Charging Door                   Suitable for manual loading of wastes and with smooth 
Dear seal equivalent of Ceramic seals with hinges.
Door Lock                          Automatic, Electric type
Ash removal door    Provided, for removing resultant bottom ash leftovers                              from the Primary chamber
Gratings    Provided
Loading Manual loading of waste
Primary Burner                        Fully automatic, with fuel, temperature and speed  controls with ignition system  flame detector                                                         Air fan Complete with safety features, flame failure                                                                    Diesel fired fuel injector type                                               
Flange mounted
Blower   Provided.  3 phase for supplying excess combustion air through the distribution system with speed control system
Temperature Minimum exit 850 0C
Observation port To be provided with protective glass type
     3.3    Secondary chamber

MEDICAL WASTE INCINERATOR (50 C 60kg/hr)

Medical Waste Incinerator, 50 to 60 Kg/hr
Support Health Sector Support Project
Point of Installation (Hospitals) Moi Voi, Makindu, Maragua, Eldama Ravine and Isiolo District Hospitals
1.    General Description
Supply, delivery, installation and commissioning of a medical waste incinerator suitable for disposal of Medical, General and Pathological waste in a safe and clean environment.  The unit shall consist of two chambers and operate on the principal of controlled air and temperature. The unit shall consist a particulate remover (scrubbers) as stipulated in waste management regulations, 2006 (Legal notice NO. 121 of 29th September, 2006).  The Unit shall be fully automatic and controlled by an automatic electronic controlled system except loading system which shall be manual.  The unit shall be capable of incinerating between 50 to 60 kg of solid medical waste per hour.  It shall be constructed from mild or aluminized steel lined with refractory material.
Main unit
Application For incineration, general and pathological
Capacity   50 C 60 kg/h burn rate
Type Two  combustion chambers type; primary  and Secondary, controlled/forced combustion air type with a flue gas emission scrubbing unit
Operating time                Minimum 8 hours daily
Operating temperature     From 850 0C to 1200 0C, Automatic controlled
Residual Ash                    5 to 10%
    3.2     Primary Chamber
Construction Constructed from heavy duty mild or aluminized  steel Or
equal and approved equivalent
Insulation material            Refractory material lining similar or equal to calcium 
Silicate and hot face combination of heavy duty brickwork
Internal Construction        Fixed hearth type complete with gratings, concave bottom
and charging door, lined with refractory material
Charging Door                   Suitable for manual loading of wastes and with smooth 
Dear seal equivalent of Ceramic seals with hinges.
Door Lock                          Automatic, Electric type
Ash removal door    Provided, for removing resultant bottom ash leftovers                              from the Primary chamber
Gratings   Provided
Loading Manual loading of waste
Primary Burner                        Fully automatic, with fuel, temperature and speed controls with ignition system, flame detector, Air fan complete with safety features, flame failure,  Diesel fired fuel injector type and Flange mounted                                                                                                    
Blower Provided. For supplying excess combustion air through the distribution system with speed control system
Temperature Minimum exit 850 0C
Observation port To be provided with protective glass type
Construction   Constructed from heavy duty mild or aluminized steel or equal and approved equivalent
Insulation Refractory material lining
Combustion Temperatures        Above 850 0C, controlled electronically
Gas residue or retention Time       > 2 second at minimum 850 0C
Secondary Burner                    Provided, Diesel fired, fully automatic, with fuel, temperature and speed controls, With ignition system,                                                                  Flame detector, Air fan, Complete with safety features, flame failure Diesel fired fuel injector type.                                                                  Flange mounted
Ejector Provided, Venturi type, for cooling the flue gases
Combustion Air Fan Provided for supplying combustion and creating a negative drift and turbulences
Temperature Maximum  1600 0C

MEDICAL WASTE INCINERATOR (50 C 60kg/hr)

Medical Waste Incinerator, 50 to 60 Kg/hr
Support Health Sector Support Project
Point of Installation (Hospitals) Moi Voi, Makindu, Maragua, Eldama Ravine and Isiolo District Hospitals
1.    General Description
Supply, delivery, installation and commissioning of a medical waste incinerator suitable for disposal of Medical, General and Pathological waste in a safe and clean environment.  The unit shall consist of two chambers and operate on the principal of controlled air and temperature. The unit shall consist a particulate remover (scrubbers) as stipulated in waste management regulations, 2006 (Legal notice NO. 121 of 29th September, 2006).  The Unit shall be fully automatic and controlled by an automatic electronic controlled system except loading system which shall be manual.  The unit shall be capable of incinerating between 50 to 60 kg of solid medical waste per hour.  It shall be constructed from mild or aluminized steel lined with refractory material.
Main unit
Application For incineration, general and pathological
Capacity   50 C 60 kg/h burn rate
Type Two  combustion chambers type; primary  and Secondary, controlled/forced combustion air type with a flue gas emission scrubbing unit
Operating time                Minimum 8 hours daily
Operating temperature     From 850 0C to 1200 0C, Automatic controlled
Residual Ash                    5 to 10%
    3.2     Primary Chamber
Construction Constructed from heavy duty mild or aluminized  steel Or
equal and approved equivalent
Insulation material            Refractory material lining similar or equal to calcium 
Silicate and hot face combination of heavy duty brickwork
Internal Construction        Fixed hearth type complete with gratings, concave bottom
and charging door, lined with refractory material
Charging Door                   Suitable for manual loading of wastes and with smooth 
Dear seal equivalent of Ceramic seals with hinges.
Door Lock                          Automatic, Electric type
Ash removal door    Provided, for removing resultant bottom ash leftovers                              from the Primary chamber
Gratings   Provided
Loading Manual loading of waste
Primary Burner                        Fully automatic, with fuel, temperature and speed controls with ignition system, flame detector, Air fan complete with safety features, flame failure,  Diesel fired fuel injector type and Flange mounted                                                                                                    
Blower Provided. For supplying excess combustion air through the distribution system with speed control system
Temperature Minimum exit 850 0C
Observation port To be provided with protective glass type
Construction   Constructed from heavy duty mild or aluminized steel or equal and approved equivalent
Insulation Refractory material lining
Combustion Temperatures        Above 850 0C, controlled electronically
Gas residue or retention Time       > 2 second at minimum 850 0C
Secondary Burner                    Provided, Diesel fired, fully automatic, with fuel, temperature and speed controls, With ignition system,                                                                  Flame detector, Air fan, Complete with safety features, flame failure Diesel fired fuel injector type.                                                                  Flange mounted
Ejector Provided, Venturi type, for cooling the flue gases
Combustion Air Fan Provided for supplying combustion and creating a negative drift and turbulences
Temperature Maximum  1600 0C

Refractory constructions incinerator

* Burning Rate                                                     (50-120kg/hour)
* Minimum Operating Temperature                (850°ϲ(Primary combustion)
* Maximum Operating Temperature               (1450°ϲ(Afterburner chamber)
* Secondary Burning Capacity                         (Compulsory)
* Density Insulation                                           (20mm high)
* Refractory Casting                                          (Minimum 65mm)
* Heavy duty refracting lining to withstand    (1500°ϲ)
* Average burn out time: Maximum                (3.0 hours)
* Fuel Type                                                          (Diesel)
* Fuel Consumption in L/hr:                            (7.5 to 9)
* Residence time in secondary chamber     (2 sec.)
* Residue ash post 100kg                               (Max. 3.8kg)
* Installation period                                            (Maximum 7days)
Type : Refractory constructions
Steel Structure 400+ Silica board + Fire Brick and
Castable between
Size : Outside – W 740 x L 1112 x H 790 / Inside – W 400 x L 800 x H 560 (mm)
Fire load of Combustion volume : 0.18 m3
Fire table area : 0.32 m2
Material : SS400 x 6.0T, Silica Board, Fire Brick (SK-36), Castable (HACT-160)
Temperature : 700 ~ 900 ℃
Residual gas combustion in secondary chambers : ≥ 2sec
Input door size : W 200 x H 200 (mm)
Ash door size : W 300 x H 400 (mm)
Type : Refractory constructions
Steel Structure 400+ Silica board + Fire Brick and Castable between
Size : Outside – W 740 x L 1112 x H 745 / Inside – W 400 x L 800 x H 600 (mm)  
Fire load of Combustion volume : 0.19 m3  
Fire table area : 0.32 m2
Material :  SS400 x 6.0T, Silica Board 50T, Fire Brick (SK-36), Castable (HACT-160)

Temperature : 1000 ~ 1100 ℃
WWW.HICLOVER.COMWaste Incinerators Auto Roll Air Filters
Nanjing Clover Medical Technology Co.,Ltd.

Tel:  +86-25-8461 0201   

Mobile: +86-13813931455(whatsapp/wechat)
Website: www.hiclover.com  
Email: [email protected]
Email: [email protected]  
Items/Model TS10(PLC) TS20(PLC) TS30(PLC) TS50(PLC) TS100(PLC)
Burn Rate (Average) 10 kg/hour 20 kg/hour 30 kg/hour 50 kg/hour 100 kg/hour
Feed Capacity(Average) 20kg 40kg 60kg 100kg 200 kg
Control Mode PLC PLC PLC PLC PLC
Combustion Chamber 100L 210L 330L 560L 1200L
Internal Dimensions 50x50x40cm 65x65x50cm 75x75x60cm 100x80x70cm 120x100x100cm
Secondary Chamber 50L 110L 180L 280L 600L
Smoke Filter Chamber Yes Yes Yes Yes Yes
Feed Mode Manual Manual Manual Manual Manual
Voltage 220V 220V 220V 220V 220V
Power 0.5Kw 0.5Kw 0.5Kw 0.7Kw 0.7Kw
Oil Consumption (kg/hour) 5.4–12.6 7.8–16.3 10.2–20 12.1–24 14–28
Gas Consumption (m3/hour) 6.2–11.4 8–15.7 9.8–20 9.9–26.1 10–32.2
Temperature Monitor Yes Yes Yes Yes Yes
Temperature Protection Yes Yes Yes Yes Yes
Oil Tank 100L 100L 100L 100L 200L
Feed Door 30x30cm 45x40cm 55x50cm 70x55cm 80x60cm
Chimney 3Meter 3Meter 5Meter 5Meter 10Meter
Chimney Type Stainless Steel Stainless Steel Stainless Steel Stainless Steel Stainless Steel
1st. Chamber Temperature 800–1000 800–1000 800–1000 800–1000 800–1000
2nd. Chamber Temperature 1000-1200 1000-1200 1000-1200 1000-1200 1000-1200
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec.
Gross Weight 1500kg 2200kg 3000kg 4500kg 6000kg
External Dimensions 140x90x120cm 160x110x130cm 175x120x140cm 230x130x155cm 260x150x180cm

Pre-assembled containerized type waste incinerator

Pre-assembled, containerized type

 Burning rate: 100 – 120kg / hour medical waste incinerator
 Minimum operating temperature: 8500c
  (Primary combustion)
Maximum operating temperature: 14500c  (afterburner chamber)
Secondary Burning capacity: Compulsory.
Density insulation: 20 mm high hospital waste incinerators
Refractory casting: minimum 65mm
Heavy duty refracting lining to withstand 15000c
Average burn out time: maximum 3.0 hrs
Fuel type: fuel oil (diesel) cannabis waste management
Fuel consumption in L/hr: 7.5 to 9
Residency time in secondary chamber: 2 secs.
Residue ash post 100kg Max 3.8 kg
Installation period Maximum 7days.
HICLOVER Solution for Fighting COVID-19, with ISO9001:2015/CE(2006/42/EC,2014/30/EU) Certification.
1. Medical Waste Incinerator(Containerized Mobile Incinerator|Top Loading Incinerator)
2. Auto Roll Air Filter for Clean Room(Air Purification)

Nanjing Clover Medical Technology Co.,Ltd.
Tel:  +86-25-8461 0201    

Mobile: +86-138139 31455
WhatsApp: 008613813931455
WhatsApp: 008615380948599
Twitter ID: @hiclovercom
Wechat: 008613813931455 (ID: hiclovercom)
Wechat: +8615380948599 (ID: wasteincinerator)
Website1: www.hiclover.com 
Email1:     [email protected]
Email2:    [email protected]    
Email3:   [email protected]  

HICLOVER Incinerator/Parts Range

Main Feature

Medical Waste Incinerators

HICLOVER 10-500kgs/Hr.Double Combustion Chambers

Single Combustion Chamber

Small, Cheap,10-20kgs/Hr.

Three Combustion Chambers(Optional)

3 Chambers for high risk waste

Pet Cremation Equipment

For Pet(small/big) Cremation Business

Animal Incineration Equipment

For other animal incineration

Items/Model TS10(PLC) TS20(PLC) TS30(PLC) TS50(PLC)
Brand HICLOVER HICLOVER HICLOVER HICLOVER
Burn Rate (Average) 10 kg/hour 20 kg/hour 30 kg/hour 50 kg/hour
Feed Capacity(Average) 20kg 40kg 60kg 100kg
Control Mode PLC PLC PLC PLC
Combustion Chamber 100L 210L 330L 560L
Internal Dimensions 50x50x40cm 65x65x50cm 75x75x60cm 100x80x70cm
Secondary Chamber 50L 110L 180L 280L
Smoke Filter Chamber Yes Yes Yes Yes
Feed Mode Manual Manual Manual Manual
Voltage 220V 220V 220V 220V
Power 0.5Kw 0.5Kw 0.5Kw 0.7Kw
Oil Consumption (kg/hour) 5.4–12.6 7.8–16.3 10.2–20 12.1–24
Gas Consumption (m3/hour) 6.2–11.4 8–15.7 9.8–20 9.9–26.1
Temperature Monitor Yes Yes Yes Yes
Temperature Protection Yes Yes Yes Yes
Oil Tank 100L 100L 100L 100L
Feed Door 30x30cm 45x40cm 55x50cm 70x55cm
Chimney 3Meter 3Meter 5Meter 5Meter
Chimney Type Stainless Steel Stainless Steel Stainless Steel Stainless Steel
1st. Chamber Temperature 800–1000 800–1000 800–1000 800–1000
2nd. Chamber Temperature 1000-1200 1000-1200 1000-1200 1000-1200
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec.
Gross Weight 1500kg 2200kg 3000kg 4500kg
External Dimensions 140x90x120cm 160x110x130cm 175x120x140cm 230x130x155cm

Items/Model

TS100(PLC)

TS150(PLC)

TS300(PLC)

TS500(PLC)

Burn Rate (Average)

100 kg/hour

150 kg/hour

300 kg/hour

500 kg/hour

Control Mode

PLC Auto.

PLC Auto.

PLC Auto.

PLC Auto.

Combustion Chamber

1200L

1500L

2000L

3000L

Internal Dimensions

120x100x100cm

150x100x100cm

170x120x100cm

210x120x120cm

Secondary Chamber

600L

750L

1000L

1500L

Smoke Filter Chamber

Dry Scrubber

Dry Scrubber

Dry Scrubber

Dry Scrubber

Feed Mode

Manual

Manual

Manual

Manual

Voltage

220V

220V

220V

220V

Power

1.38Kw

1.69Kw

2.57Kw

4.88Kw

Diesel Oil Consumption (kg/hour)

Ave.20.4

Ave.24.2

Ave.33

Ave.44

Natural Gas Consumption (m3n/hour)

Ave.24.5

Ave.29

Ave.39.6

Ave.52.8

Temperature Monitor

Yes

Yes

Yes

Yes

Temperature Protection

Yes

Yes

Yes

Yes

Oil Tank

200L

300L

500L

500L

Chimney

10Meter

10Meter

14Meter

14Meter

Chimney Type

Stainless Steel

Stainless Steel

Stainless Steel

Stainless Steel

1st. Chamber Temperature

800–1000

800–1000

800–1000

800–1000

2nd. Chamber Temperature

1000-1200

1000-1200

1000-1200

1000-1200

Residency Time

2.0 Sec.

2.0 Sec.

2.0 Sec.

2.0 Sec.

Gross Weight

6000kg

8500kg

11000kg

16000kg

External Dimensions

260x150x180cm

300x160x190cm

400x210x300cm

450x210x300cm

CE and ISO Certification Pass Incinerators

 

2021-03-02

small medical waste incinerator

small medical waste incinerator

small medical waste incinerator design with PLC( Programmable Logic Controller), Intelligent and Automatic operation. Set combuston time according to different waste material and incinerator stop combustion itself. Set temperature protection parameter, if the temperature overheat, incinerator stop combustion itself.

Items/Model TS10(PLC) TS20(PLC) TS30(PLC) TS50(PLC) TS100(PLC)
Burn Rate 10 kg/hour 20 kg/hour 30 kg/hour 50 kg/hour 100 kg/hour
Feed Capacity 20kg 40kg 60kg 100kg 200 kg
Control Mode PLC PLC PLC PLC PLC
Combustion Chamber 100L 210L 330L 560L 1200L
Internal Dimensions 50x50x40cm 65x65x50cm 75x75x60cm 100x80x70cm 120x100x100cm
Secondary Chamber 50L 110L 180L 280L 600L
Smoke Filter Chamber Yes Yes Yes Yes Yes
Feed Mode Manual Manual Manual Manual Manual
Voltage 220V 220V 220V 220V 220V
Power 0.5Kw 0.5Kw 0.5Kw 0.7Kw 0.7Kw
Oil Consumption (kg/hour) 5.4–12.6 7.8–16.3 10.2–20 12.1–24 14–28
Gas Consumption (m3/hour) 6.2–11.4 8–15.7 9.8–20 9.9–26.1 10–32.2
Temperature Monitor Yes Yes Yes Yes Yes
Temperature Protection Yes Yes Yes Yes Yes
Oil Tank 100L 100L 100L 100L 200L
Feed Door 30x30cm 45x40cm 55x50cm 70x55cm 80x60cm
Chimney 3Meter 3Meter 5Meter 5Meter 10Meter
Chimney Type Stainless Steel Stainless Steel Stainless Steel Stainless Steel Stainless Steel
1st. Chamber Temperature 800℃–1000℃ 800℃–1000℃ 800℃–1000℃ 800℃–1000℃ 800℃–1000℃
2nd. Chamber Temperature 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec.
Gross Weight 1500kg 2200kg 3000kg 4500kg 6000kg
External Dimensions 140x90x120cm 160x110x130cm 175x120x140cm 230x130x155cm 260x150x180cm

portable incinerator

portable incinerator

portable incinerator means a small incinerator so end user can move it to other place. we made portable incinerator and the weight under 2000 kgs, the burning rate from 5kgs per hour to 20kgs per hour. all designed with three combustion chamber and two oil or gas burner. this kind of portable incinerator is cheap cost for small waste out put.

Items/Model YD-10C YD-20C
Burning Rate (kgs/Hour) 10 kgs/Hr. 20 kgs/Hr.
Feed Capacity (kgs) 40 kgs 40 kgs
Equipment Weight 2100 kgs 2100 kgs
Primary Chamber (Liters) 200 200
Secondary Chamber (Liters) 140 140
External Dimensions (cm) 170x140x160 170x140x160
Internal Dimensions (cm) 55x55x65 55x55x65
Oil Tank(Liters) 50 100
Door Opening (cm) 38 x 48 38 x 48
Chimney (M) 5 5
Chimney Type Stainless Steel Stainless Steel
Secondary Chamber YES YES
Mix-Combustion Chamber YES YES
Smoke Filter Chamber YES YES
Combustion Fuel Oil/Gas Oil/Gas
Residency Time 2.0 Sec. 2.0 Sec.
Temperature Monitoring YES YES
1st. Chamber Temperature 800℃–1000℃ 800℃–1000℃
2nd. Chamber Temperature 1000℃-1200℃ 1000℃-1200℃