small scale incinerator means small burning rate (capacity), average from 5kgs per hour to 20 kgs per hour. this kind of incinerator mainly for small hospital clinic or laboratory, etc. but all of them design with double combustion chamber to best waste treatment. some place or department, small scale incinerator is necessary for goverment rule request and the end user need a simple cheap equipment, you can contact with to design with more cheaper cost but simple for you.

Items/Model YD-10C YD-20C YD-30C
Burning Rate (kgs/Hour) 10 kgs/Hr. 20 kgs/Hr. 30 kgs/Hr.
Feed Capacity (kgs) 40 kgs 40 kgs 50 kgs
Equipment Weight 2100 kgs 2100 kgs 2300 kgs
Primary Chamber (Liters) 200 200 250
Secondary Chamber (Liters) 140 140 140
External Dimensions (cm) 170x140x160 170x140x160 170x140x190
Internal Dimensions (cm) 55x55x65 55x55x65 55x55x85
Oil Tank(Liters) 50 100 100
Door Opening (cm) 38 x 48 38 x 48 38 x 48
Chimney (M) 5 5 5
Chimney Type Stainless Steel Stainless Steel Stainless Steel
Secondary Chamber YES YES YES
Mix-Combustion Chamber YES YES YES
Smoke Filter Chamber YES YES YES
Combustion Fuel Oil/Gas Oil/Gas Oil/Gas
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec.
Temperature Monitoring YES YES YES
1st. Chamber Temperature 800℃–1000℃ 800℃–1000℃ 800℃–1000℃
2nd. Chamber Temperature 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃

No.    Parameter    Standards, Guideline, Criteria and Procedure
1    Basic Plant Design    An approved plant must have four distinct sections that demonstrate three principles of
Turbulence, Residence Time and Temperature are inbuilt in the plant design .The
regulated sections may include but not limited to:

Overall plant layout. Feed chamber/ charging
Primary Combustion Chamber. Secondary Combustion Chamber. Particulate Scrubbers
Acid Gas Scrubbers The stack/ chimney.
2    Feeding And Charging    Controlled hygienic, mechanical or automatic feeding methods have to be used which
will not influence the air temperature in the primary and secondary chambers of the
incinerator negatively.

No waste is to be fed into the incinerator:

1.    Until the minimum temperatures have been reached.

2.    If the minimum combustion temperatures are not maintained.
3.    Whenever the previous charge has not been completely combusted in the case of batch feeding.

4.    Until such time as the addition of more waste will not cause the design parameters of the incinerator to be exceeded.
3    Primary  Combustion
Chamber    The primary combustion chamber must:

1.    Be accepted as the primary combustion zone.
2.    Be equipped with a burner/s burning gas/fuel or low sulphur liquid fuels.
Other combustion methods will be judged on merits.

3.    Ensure primary air supply is controlled efficiently

4.    Ensure minimum exit temperature is not less than 850oC
4    Secondary
Combustion Chamber
(Afterburner).    The secondary combustion chamber must:

1.    Be accepted as secondary combustion zone.
2.    Be fitted with secondary burner/s burning gas or low sulphur liquid fuel or any suitable fuel.

3.    Ensure secondary air supply is controlled efficiently.

4.    Ensure flame contact with all gases is achieved.

5.    Ensure residence time is not less than two (2) seconds.
6.    Ensure the gas temperature as measured against the inside wall in the secondary chamber & not in the flame zone, is not less than 1100oC.

7.    Ensure the oxygen content of the emitted gases is not less than 11%.
8.    Ensure both primary and the combustion temperatures are maintained until all waste has been completely combusted
5    Particulate Removers    A mechanical particulate collector must be incorporated after secondary combustion
chamber for removal of particulate pollutants entrained in the flue gas stream. The
particulate collectors may include any of the following or a combination thereof:

22

Cyclone separator Electrostatic precipitators Fabric filters
6    Chimney / Stack    1.    The chimney should have a minimum height of 10 meters above ground level
and clear the highest point of the building by not less than 3 meters for all
roofs. The topography and height of adjacent buildings within 50 meters radius should be taken into account.

2.    If possible the chimney should be visible to the operator from the feeding area.
3.    The addition of dilution air after combustion in order to achieve the
requirement of these guidelines is unacceptable.

4.    The minimum exit velocity should be 10 m/s and at least twice the surrounding wind speed (Efflux velocity = wind speed x 2) whichever is higher to ensure no down washing of exiting gases.

5.    Point for the measurement of emissions shall be provided.
7    Instrumentation    Instrument for determining the inside wall temperature and not burner flame
temperature must be provided for both primary and secondary chambers.

2.    An audible and visible alarm must be installed to warn the operator when the secondary temperature drops to below the required temperature.

3.    In addition to the above the following instruments may also be required.

A carbon monoxide and/or oxygen meter/recorder A smoke density meter/recorder
A gas flow meter/recorder

A solid particulate meter/recorder

Any other instrument or measurement that may be considered necessary
8    Emission Limits    1.    Combustion efficiency:

Combustion efficiency (CE) shall be at least 99.00% The Combustion efficiency is computed as follows;

C.E=    % CO 2    x 100
% CO2 + CO
2.    The temperature of the primary chamber shall be 800 ± 50o C
3.    The secondary chamber gas residence time shall be at least 1 (one) second at 1050 ± 50o C, with 3% Oxygen in the stack gas.

4    Opacity of the smoke must not exceed 20% Viewed from 50 meters with naked eyes
5.    All the emission to the air other than steam or water vapour must be odourless
and free from mist, fume and droplets.

6.    The Authority may require that the certificate holder have tests carried out by an accredited institution to determine stack and/or ground level concentrations of the following substances.

No

Cadmium and compounds as    Cd Mercury    Hg
Thallium    Tl

Chromium    Cr
Beryllium    Be
Arsenic    As
Antimony    Sb
Barium    Ba
Lead    Pb
Silver    Ag
Cobalt    Co
Copper    Cu
Manganese    Mn
Tin    Sn
Vanadium    V
Nickel    Ni
Hydrochloric    HCL
Hydrofluoric acid    HF
Sulphur dioxide    S02
A 99.99% destruction and removal efficiency (DRE) for each principal organic hazardous constituent (POHC) in the waste feed where:

DRE = [(Win – Wout)/Win]*100
Where: Win = mass feed rate of the POHC in the waste stream fed to incinerator, and
Wout = mass emission rate of POHC in the stack prior to the release to the
atmosphere.

The average dioxin and furan concentration in the emissions should not exceed 80ng/m3 total dioxins and furans if measured for a period of 6 to 16 hours.

te:
All pollutant concentrations must be expressed at Oo C and 1.013 x 10 5 N/m2,
dry gas and 11% oxygen correction.

Oxygen correction is computed as:

Es =    21 – Os   x EM 21 – OM
Where:  Es    = Calculated   emission concentration at the standard percentage oxygen concentration
EM    = Measured emission concentration
Os    = Standard oxygen concentration
OM    = measured oxygen concentration

we are famous brand(Hiclover) china incinerator manufacturer and all over the world. We supply single combustion chamber, double combustion chambers, three combustion chambers and multi-combustion chambers waste incinerators for laboratory, clinic, hospital, medical center, hygiene clinical waste destruction with medical disposable, biological waste, medical plastic waste, hazardous waste, red bag waste, needle disposal, gauze and bandages, sealed sharp containers, pathological waste, trace-chemotherapeutic wastes, etc. china incinerator manufacturer supply better product and better price for customer.

Key Features:
●Full range incinerator with Economized Small Scale incinerator, Standard Small-Large Scale incinerator, General Municipal Solid Waste Incinerator, Pet and Animal Cremation, Containerized Mobile Incinerator, High Efficient Environmental Waste Incinerator.
● Single combustion chamber, double combustion chambers, three combustion chambers and multi-combustion chambers waste incinerators.
● System solutions for medical waste environmental.
● High burn rate, from 5kgs to 1000kgs per hour.
● New Design for pet animal cremation business.
● HICLOVER, trusted partner with years of experience.

Items/Model TS10(PLC) TS20(PLC) TS30(PLC) TS50(PLC) TS100(PLC)
Burn Rate 10 kg/hour 20 kg/hour 30 kg/hour 50 kg/hour 100 kg/hour
Feed Capacity 20kg 40kg 60kg 100kg 200 kg
Control Mode PLC PLC PLC PLC PLC
Combustion Chamber 100L 210L 330L 560L 1200L
Internal Dimensions 50x50x40cm 65x65x50cm 75x75x60cm 100x80x70cm 120x100x100cm
Secondary Chamber 50L 110L 180L 280L 600L
Smoke Filter Chamber Yes Yes Yes Yes Yes
Feed Mode Manual Manual Manual Manual Manual
Voltage 220V 220V 220V 220V 220V
Power 0.5Kw 0.5Kw 0.5Kw 0.7Kw 0.7Kw
Oil Consumption (kg/hour) 5.4–12.6 7.8–16.3 10.2–20 12.1–24 14–28
Gas Consumption (m3/hour) 6.2–11.4 8–15.7 9.8–20 9.9–26.1 10–32.2
Temperature Monitor Yes Yes Yes Yes Yes
Temperature Protection Yes Yes Yes Yes Yes
Oil Tank 100L 100L 100L 100L 200L
Feed Door 30x30cm 45x40cm 55x50cm 70x55cm 80x60cm
Chimney 3Meter 3Meter 5Meter 5Meter 10Meter
Chimney Type Stainless Steel Stainless Steel Stainless Steel Stainless Steel Stainless Steel
1st. Chamber Temperature 800℃–1000℃ 800℃–1000℃ 800℃–1000℃ 800℃–1000℃ 800℃–1000℃
2nd. Chamber Temperature 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec.
Gross Weight 1500kg 2200kg 3000kg 4500kg 6000kg
External Dimensions 140x90x120cm 160x110x130cm 175x120x140cm 230x130x155cm 260x150x180cm

•    A burn rate of 25 – 30kg/hr.
•    Consists of two chambers to ensure significant reduction of emissions and be capable of temperatures in the range of 800-1000˚c.
•    Incinerator must be of a low maintenance design, be diesel fuelled and need no more than 15 amp 220-250 V power. KW consumption per hour should be stated
•    The incinerator should also be able to run off a generator.
•    The incinerator should have option of tank and should use no more than 12L of diesel fuel per hour to burn 25- 30kg of waste
•    Design must be such to minimize risk to operators and have a simple start sequence to minimize operator training and skills
•    Solid waste reductions in the range of 90 – 97% should be routinely achievedWhat  are  main  differences  between  medical  incinerators:    YD-10C  and  TS10(PLC)?
(2)  After  combustion,  the  medical  waste  becomes  smoke?  Without  smell?  No  pollution?
(3)  What  should  we  do  to  release  the  smoke?    Prepare  a  pipe  to  direct  the  smoke  to  factory  outside?
(4)  Any  operation  guide  for  reference,  we  worry  that  it’s  difficult  to  operate?
(5)  YD-10C  and  TS10(PLC)  are  the  smallest  scale  incinerator?    What  are  their  prices  and  warranty  period?

New continued feeding incinerator is valid for large scale incinerator, main function including a.)waste feeding system, b.)incinerator mainbody, c.)wet scrubber system. Burning rate up to 500kgs per hour and 4.7m3 primary combustion chamber capacity.incinerator-wet-scrubber-system1-762x294

Waste Auto-Feeding →→

Shredder System→→

Primary Combustion Chamber→→

Mix & Secondary Combustion Chamber

Wet Spray Scrubber→→

Wet Dust Scrubber→→

Cyclone Filter & Separator→→

Chimney

small incinerator with primary combustion chamber 200Liters to 400Liters. this is good idea and capacity for small pets like cat, bird and small dog and other some other medical waste from clinic.incinerator 9

Animal diseases, new virus strains and spread of infectious diseases are only few of the consequences of improper animal waste treatment. Incineration is the way forward for Bio-secure waste disposal. Modern incineration is recognized as a most efficient solution for significant risk reduction in animal waste management.

pet incineration equipment is for family pet cremation. our pet incineration equipment made with double combustion chamber, waste oil collect function, movable feeding door and also stainless steel material chimney, italy burners, etc.

we are animal waste incinerator manufacturer, the combustion chamber volume up to 5.5m3 for big animal and also make small incinerator for pets and small animals.

Items/Model A360 A600 A900 A1200
Burning Rate *animal 20 kgs/Hr. 20 kgs/Hr. 30 kgs/Hr. 60 kgs/Hr.
Feed Capacity *animal 30 kgs 50 kgs 80 kgs 100 kgs
Equipment Weight 2300 kgs 3000 kgs 4000 kgs 4300 kgs
Primary Chamber (Liters) 360 600 900 1200
Secondary Chamber (Liters) 200 200 300 500
External Dimensions (cm) 145x90x175 175 x 100 x 180 200x160x230 220x180x360
Internal Dimensions (cm) 100x60x60 130 x 70 x 65 120x90x85 130x100x90
Oil Tank(Liters) 200 200 300 300
Door Opening (cm) 48 x 60 50 x 60 62 x 80 55 x 80
Chimney (M) 5 5 5 10
Chimney Type Stainless Steel Stainless Steel Stainless Steel Stainless Steel
Secondary Chamber YES YES YES YES
Mix-Combustion Chamber YES YES YES YES
Smoke Filter Chamber YES YES YES YES
Combustion Fuel Oil/Gas Oil/Gas Oil/Gas Oil/Gas
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec.
Temperature Monitoring YES YES YES YES
1st. Chmaber Temperature 800℃–1000℃ 800℃–1000℃ 800℃–1000℃ 800℃–1000℃
2nd. Chmaber Temperature 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃ 1000℃-1200℃

The pet cremation equipment humanized design with movable platform, small space covers for modern pet cremation business owner all over the world. animal incinerator cost is key point for pet cremation business owners. our pet incineration equipment made with double combustion chamber, waste oil collect function, movable feeding door.

Items/Model A360 A600 A900 A1200
Burning Rate *animal 20 kgs/Hr. 20 kgs/Hr. 30 kgs/Hr. 60 kgs/Hr.
Feed Capacity *animal 30 kgs 50 kgs 80 kgs 100 kgs
Equipment Weight 2300 kgs 3000 kgs 4000 kgs 4300 kgs
Primary Chamber (Liters) 360 600 900 1200
Secondary Chamber (Liters) 200 200 300 500
External Dimensions (cm) 145x90x175 175 x 100 x 180 200x160x230 220x180x360
Internal Dimensions (cm) 100x60x60 130 x 70 x 65 120x90x85 130x100x90
Oil Tank(Liters) 200 200 300 300
Door Opening (cm) 48 x 60 50 x 60 62 x 80 55 x 80
Chimney (M) 5 5 5 10
Chimney Type Stainless Steel Stainless Steel Stainless Steel Stainless Steel
Secondary Chamber YES YES YES YES
Mix-Combustion Chamber YES YES YES YES
Smoke Filter Chamber YES YES YES YES
Combustion Fuel Oil/Gas Oil/Gas Oil/Gas Oil/Gas
Residency Time 2.0 Sec. 2.0 Sec. 2.0 Sec. 2.0 Sec.
Temperature Monitoring YES YES YES YES
1st. Chmaber Temperature 800℃–1000℃ 800℃–1000℃ 800℃–1000℃ 800℃–1000℃